Issue # Subject Category Type Status % Completed Last updated at
124Power issues L.A.DatacenterIncidentResolved
100%
2018-01-04 20:38:47
CrownCloud - Status - Power issues L.A.

Updates on this issue

2017-12-17 12:28:10

VPSes are starting up one-by-one, Please standby for further updates.

2017-12-17 12:03:34

Node is booting up. Will keep this status message posted as we get more information from the node.

2017-12-17 11:19:11

LA19 still under fsck / file system check. Around 30% done so far. Should speedup as we go forward.

2017-12-16 23:34:06

Everything is online except LA19. FSCK / File system check running on LA19.

2017-12-16 20:43:18

Update - Work is done, being checked for faults and will energize in about 10 minutes. 
Dec 16, 11:41 PST

2017-12-16 20:26:08

Update - We are waiting for a proper ETA from electricians. We apologize for the increasing estimates of completion. 
Dec 16, 11:21 PST

2017-12-16 19:59:45

Update - Further delays in this repair, at least 30 minutes additional repair time. 
Dec 16, 10:57 PST

2017-12-16 18:47:21

Update - Electricians expect power to be restored by 10:30AM. Updates to follow. 
Dec 16, 09:46 PST

2017-12-16 18:40:35

Update - The problem has been back traced to a failed main breaker, electricians are currently replacing the breaker. 
Dec 16, 09:39 PST

2017-12-16 18:32:59

We are still waiting on updates from the datacenter. As mentioned on their own status page ( http://status.quadranet.com/ ) it appears that the whole building/floor is affected by the issue.

2017-12-16 17:58:12

Update - Technicians are currently working to restore power, bypassing the failed UPS unit. 
Dec 16, 08:55 PST

2017-12-16 17:38:52

There appear to be power related issues in the LA facility.
We are waiting for the datacenter to provide more details about this incident.